CIE-A 200 Fire Alarm Panel
EN54 single loop addressable fire alarm panel
Key Features
- Operating temperature: +5°C to +40°C
- IP30 rating
- 230V AC nominal main supply input
- Standby battery requirement 2 x 7Ah 12V sealed lead acid (2 x 12 Ah with extended battery box)
- 1 loop maximum
- 2000 metres maximum loop length
- 24 Ohms maximum conductor resistance
- 450 DLU loop loading (200 devices maximum)*
- 40V DC loop operating Voltage
- 24V DC standby
- 500mA maximum loop current
- 32 supported zones
- LCD graphical display
- 31 characters for each device label
- 2 x monitored inputs (3k3 eol, 680r firing resistor)
- 3 x volt free relay (30v dc @ 1a max)
- Monitored outputs 2 x (24v dc @ 500ma max, 10k eol)
Fire Alarm Panel
Fire Alarm Panel
Cat No |
Description |
Max Battery Type & Size |
FP-021 |
CIE-A 200 single loop panel |
2 x 7Ah integrally (can use 2 x 12Ah batteries using FPA-1005 battery conversion kit) |
FPR-021 |
CIE-A 200 repeater panel |
2 x 7Ah |
Cat No
Description
Max Battery Type & Size
|
FP-021
CIE-A 200 single loop panel
2 x 7Ah integrally (can use 2 x 12Ah batteries using FPA-1005 battery conversion kit)
|
Cat No
Description
Max Battery Type & Size
|
FPR-021
CIE-A 200 repeater panel
2 x 7Ah
|
|
Cat No |
Description |
 |
FPA-381 |
CIE-A 200 panel recessing cradle |
 |
FPA-1005 |
Battery conversion kit (holds 2 x 12Ah batteries to give additional standby capacity up to 72 hours) |
|
Cat No
Description
|
FPA-381
CIE-A 200 panel recessing cradle
|
|
Cat No
Description
|
FPA-1005
Battery conversion kit (holds 2 x 12Ah batteries to give additional standby capacity up to 72 hours)
|
Specification / Technical Information
Batteries to be ordered separately