LPAC Single Phase Static Inverters

BSI-certified static inverter systems designed to EN 50171 specifications

LPAC Single Phase Static Inverters

BSI-certified static inverter systems designed to EN 50171 specifications

Key Features

  • Designed to the latest European EN50171 Specification
  • True sinewave & PWM microprocessor controlled technology up to 97% efficiency
  • System and battery test function
  • Capable of 120% continuous overload to meet European Emergency Lighting regulations
  • Larger charger for faster recharge of batteries Ultra-fast changeover mode to battery mode
  • Two way built-in distribution panel (optional 4 way)
  • LCD panel providing accurate detailed information about load, batteries, system diagnostics and manual testing facility & audible alarm
  • RS232 and dry contacts for communication and remote monitoring internal selfcontained battery system
  • Generator compatible
  • Remote monitoring panel (optional)

Model/Power Rating

Power Rating VA/W

Power Factor

Efficiency at 100% load

Operating Temperature (Ambient)

Serial Communication

Altitude

Protection Degree

Noise level at 1m

Standard

Input Voltage/Tolerance

Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Short Circuit Protection

Overload Capacity

Battery Type

Float Charging Value

End of Discharge Voltage

Battery Ambient Temperature

Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

LPAC500
500/400
0.8
>97%
0-40°C
Dry contacts plus RS232
<1000 Metres (above sea level)
IP21
<56 dBA
Emergency lighting EN50171
230 Vac single phase /184V ~ 285V
50Hz ± 5%
EN50091-2 CLASS A
230 Vac single phase
Changeover mode ± 10)% / battery mode ± 3%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Electronic short circuit
120% continuous, 150% alarm load
Sealed lead acid - maintenance free
54Vdc
42Vdc
20°C
Automatic battery test / smart battery management
Double pole DC circuit breaker
750 x 250 x 850
120

Model/Power Rating

Power Rating VA/W

Power Factor

Efficiency at 100% load

Operating Temperature (Ambient)

Serial Communication

Altitude

Protection Degree

Noise level at 1m

Standard

Input Voltage/Tolerance

Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Short Circuit Protection

Overload Capacity

Battery Type

Float Charging Value

End of Discharge Voltage

Battery Ambient Temperature

Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

LPAC1250
1250/1000
0.8
>97%
0-40°C
Dry contacts plus RS232
<1000 Metres (above sea level)
IP21
<56 dBA
Emergency lighting EN50171
230 Vac single phase /184V ~ 285V
50Hz ± 5%
EN50091-2 CLASS A
230 Vac single phase
Changeover mode ± 10)% / battery mode ± 3%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Electronic short circuit
120% continuous, 150% alarm load
Sealed lead acid - maintenance free
54Vdc
42Vdc
20°C
Automatic battery test / smart battery management
Double pole DC circuit breaker
750 x 250 x 1250
195

Model/Power Rating

Power Rating VA/W

Power Factor

Efficiency at 100% load

Operating Temperature (Ambient)

Serial Communication

Altitude

Protection Degree

Noise level at 1m

Standard

Input Voltage/Tolerance

Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Short Circuit Protection

Overload Capacity

Battery Type

Float Charging Value

End of Discharge Voltage

Battery Ambient Temperature

Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

LPAC3000
3000/2400
0.8
>97%
0-40°C
Dry contacts plus RS232
<1000 Metres (above sea level)
IP21
<56 dBA
Emergency lighting EN50171
230 Vac single phase /184V ~ 285V
50Hz ± 5%
EN50091-2 CLASS A
230 Vac single phase
Changeover mode ± 10)% / battery mode ± 3%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Electronic short circuit
120% continuous, 150% alarm load
Sealed lead acid - maintenance free
54Vdc
42Vdc
20°C
Automatic battery test / smart battery management
Double pole DC circuit breaker
750 x 400 x 1250
445
  • Use basic catalogue number, e.g. LPAC1250
  • Add suffix /3 for standard 3 hour duration (systems for 1 hour duration can be manufactured to order, add suffix /1)
  • Example ordering code is now LPAC1250/3 (1250VA single phase static inverter system for 3 hours duration)

Specification / Technical Information

Orbik’s highly trained technical after-sales team are committed to ensuring that our customer’s requirements continue to be met from the initial sales enquiry all the way through to the maintenance and
commissioning of lighting systems.

By identifying and responding to individual customer’s specific requirements, we have gained a reputation for excellent technical support, which has enabled our products to be at the forefront of many prestigious installations throughout the UK and overseas.

Our technical department are equipped to provide lighting solutions to even the most demanding of installations and can offer the client total peace-ofmind by providing photometric data and other lighting design information, including luminaire data files.

For further information, contact our technical department at [email protected].

Quick Enquiry

or call us on +44 (0) 1922 745024

0/250 Characters