HPAC Single Phase Static Inverters

BSI-certified static inverter systems that meet European Emergency Lighting regulations

HPAC Single Phase Static Inverters

BSI-certified static inverter systems that meet European Emergency Lighting regulations

Key Features

  • True double-conversion and PWM technology
  • Inverter stage output Galvanic isolation transformer included
  • Capable of 120% continuous overload to meet European Emergency Lighting regulations
  • Parallel mode operation (optional) (hot standby, redundant, symmetric parallel)
  • Larger 20 Amp charger for faster recharge of batteries
  • Maintenance by-pass (for complete isolation of the inverter during maintenance)
  • Unique Inverter design to suit high inrush lighting loads
  • Bypass to load (changeover mode) user selection
  • LCD panel providing accurate detailed information about the Load, Batteries and Inverter with advanced diagnostics.
  • 3 Microprocessors; main control board, rectifier board, optional parallel control board
  • Real time clock and calendar indicator
  • 64 Recorded real-time events history
  • RS232 and dry contacts for communication and remote monitoring
  • Designed and manufactured under ISO9001 certification

Cat No

Output Rating KvA

Output Rating Kw

Power Factor

Serial Communication

Protection Degree

Operating Temp. (Ambient)

Standard

Ventilation

Altitude

Relative Humidity

Acoustic Noise at 1m

Voltage/Tolerance

Bypass Voltage

Input Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Frequency Tolerance

Efficiency at 100% Load

Crest Factor

Short Circuit Protection

Overload Capacity

Total Harmonic Distortion

Battery Type

Number of 12V Blocks

Float Charging Value

End of Discharge Voltage

Battery Charging Characteristics

Battery Ambient Temperature

Automatic Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

HPAC4
4
3.2
0.8
Dry contacts plus RS232
IP41
0-40°C
Emergency lighting EN50171
Forced air cooling
<1000 Metres (above sea level)
90% maximum (non-condensing)
<56 dBA
230Vac single phase, 4 wires + ground / ± 15%
230Vac single phase
50Hz ± 5% (60Hz to order)
EN 50091-2 class A
230Vac single phase
Static (balanced load) ± 1%
Static (unbalanced load) ± 2%
Dynamic (step load 0-100%) ± 5%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Line synchronised ± 1%
Free running ± 0.2%
>87-91%
3:1
Electronic short circuit
120% continuous, 150% load 10 minutes, 180% load 1 minute, 200% load for 1 second
Linear load <3%
Non-linear load 75% NP and CF 3:1) <5%
Sealed lead acid - maintenance free
16
216Vdc
160Vdc
Electronic short circuit
25°C
Weekly
Circuit breaker
300 x 500 x 1220
85

Cat No

Output Rating KvA

Output Rating Kw

Power Factor

Serial Communication

Protection Degree

Operating Temp. (Ambient)

Standard

Ventilation

Altitude

Relative Humidity

Acoustic Noise at 1m

Voltage/Tolerance

Bypass Voltage

Input Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Frequency Tolerance

Efficiency at 100% Load

Crest Factor

Short Circuit Protection

Overload Capacity

Total Harmonic Distortion

Battery Type

Number of 12V Blocks

Float Charging Value

End of Discharge Voltage

Battery Charging Characteristics

Battery Ambient Temperature

Automatic Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

HPAC5
5
4
0.8
Dry contacts plus RS232
IP41
0-40°C
Emergency lighting EN50171
Forced air cooling
<1000 Metres (above sea level)
90% maximum (non-condensing)
<56 dBA
230Vac single phase, 4 wires + ground / ± 15%
230Vac single phase
50Hz ± 5% (60Hz to order)
EN 50091-2 class A
230Vac single phase
Static (balanced load) ± 1%
Static (unbalanced load) ± 2%
Dynamic (step load 0-100%) ± 5%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Line synchronised ± 1%
Free running ± 0.2%
>87-91%
3:1
Electronic short circuit
120% continuous, 150% load 10 minutes, 180% load 1 minute, 200% load for 1 second
Linear load <3%
Non-linear load 75% NP and CF 3:1) <5%
Sealed lead acid - maintenance free
18
243Vdc
180Vdc
Electronic short circuit
25°C
Weekly
Circuit breaker
300 x 500 x 1220
95

Cat No

Output Rating KvA

Output Rating Kw

Power Factor

Serial Communication

Protection Degree

Operating Temp. (Ambient)

Standard

Ventilation

Altitude

Relative Humidity

Acoustic Noise at 1m

Voltage/Tolerance

Bypass Voltage

Input Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Frequency Tolerance

Efficiency at 100% Load

Crest Factor

Short Circuit Protection

Overload Capacity

Total Harmonic Distortion

Battery Type

Number of 12V Blocks

Float Charging Value

End of Discharge Voltage

Battery Charging Characteristics

Battery Ambient Temperature

Automatic Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

HPAC6
6
4.8
0.8
Dry contacts plus RS232
IP41
0-40°C
Emergency lighting EN50171
Forced air cooling
<1000 Metres (above sea level)
90% maximum (non-condensing)
<56 dBA
230Vac single phase, 4 wires + ground / ± 15%
230Vac single phase
50Hz ± 5% (60Hz to order)
EN 50091-2 class A
230Vac single phase
Static (balanced load) ± 1%
Static (unbalanced load) ± 2%
Dynamic (step load 0-100%) ± 5%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Line synchronised ± 1%
Free running ± 0.2%
>87-91%
3:1
Electronic short circuit
120% continuous, 150% load 10 minutes, 180% load 1 minute, 200% load for 1 second
Linear load <3%
Non-linear load 75% NP and CF 3:1) <5%
Sealed lead acid - maintenance free
18
243Vdc
180Vdc
Electronic short circuit
25°C
Weekly
Circuit breaker
300 x 500 x 1220
110

Cat No

Output Rating KvA

Output Rating Kw

Power Factor

Serial Communication

Protection Degree

Operating Temp. (Ambient)

Standard

Ventilation

Altitude

Relative Humidity

Acoustic Noise at 1m

Voltage/Tolerance

Bypass Voltage

Input Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Frequency Tolerance

Efficiency at 100% Load

Crest Factor

Short Circuit Protection

Overload Capacity

Total Harmonic Distortion

Battery Type

Number of 12V Blocks

Float Charging Value

End of Discharge Voltage

Battery Charging Characteristics

Battery Ambient Temperature

Automatic Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

HPAC8
8
6.4
0.8
Dry contacts plus RS232
IP41
0-40°C
Emergency lighting EN50171
Forced air cooling
<1000 Metres (above sea level)
90% maximum (non-condensing)
<56 dBA
230Vac single phase, 4 wires + ground / ± 15%
230Vac single phase
50Hz ± 5% (60Hz to order)
EN 50091-2 class A
230Vac single phase
Static (balanced load) ± 1%
Static (unbalanced load) ± 2%
Dynamic (step load 0-100%) ± 5%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Line synchronised ± 1%
Free running ± 0.2%
>87-91%
3:1
Electronic short circuit
120% continuous, 150% load 10 minutes, 180% load 1 minute, 200% load for 1 second
Linear load <3%
Non-linear load 75% NP and CF 3:1) <5%
Sealed lead acid - maintenance free
20
270Vdc
200Vdc
Electronic short circuit
25°C
Weekly
Circuit breaker
300 x 500 x 1220
125

Cat No

Output Rating KvA

Output Rating Kw

Power Factor

Serial Communication

Protection Degree

Operating Temp. (Ambient)

Standard

Ventilation

Altitude

Relative Humidity

Acoustic Noise at 1m

Voltage/Tolerance

Bypass Voltage

Input Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Frequency Tolerance

Efficiency at 100% Load

Crest Factor

Short Circuit Protection

Overload Capacity

Total Harmonic Distortion

Battery Type

Number of 12V Blocks

Float Charging Value

End of Discharge Voltage

Battery Charging Characteristics

Battery Ambient Temperature

Automatic Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

HPAC12
12.5
10
0.8
Dry contacts plus RS232
IP41
0-40°C
Emergency lighting EN50171
Forced air cooling
<1000 Metres (above sea level)
90% maximum (non-condensing)
<56 dBA
230Vac single phase, 4 wires + ground / ± 15%
230Vac single phase
50Hz ± 5% (60Hz to order)
EN 50091-2 class A
230Vac single phase
Static (balanced load) ± 1%
Static (unbalanced load) ± 2%
Dynamic (step load 0-100%) ± 5%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Line synchronised ± 1%
Free running ± 0.2%
>87-91%
3:1
Electronic short circuit
120% continuous, 150% load 10 minutes, 180% load 1 minute, 200% load for 1 second
Linear load <3%
Non-linear load 75% NP and CF 3:1) <5%
Sealed lead acid - maintenance free
20
270Vdc
200Vdc
Electronic short circuit
25°C
Weekly
Circuit breaker
300 x 500 x 1220
155

Cat No

Output Rating KvA

Output Rating Kw

Power Factor

Serial Communication

Protection Degree

Operating Temp. (Ambient)

Standard

Ventilation

Altitude

Relative Humidity

Acoustic Noise at 1m

Voltage/Tolerance

Bypass Voltage

Input Frequency

Maximum RFI

Output Voltage

Voltage Stability

Voltage Recovery Time

Frequency

Frequency Tolerance

Efficiency at 100% Load

Crest Factor

Short Circuit Protection

Overload Capacity

Total Harmonic Distortion

Battery Type

Number of 12V Blocks

Float Charging Value

End of Discharge Voltage

Battery Charging Characteristics

Battery Ambient Temperature

Automatic Battery Test

Battery Protection

Dimensions W x D x H (mm)

Weight (Kg)

HPAC20/SP
20
14
0.8
Dry contacts plus RS232
IP41
0-40°C
Emergency lighting EN50171
Forced air cooling
<1000 Metres (above sea level)
90% maximum (non-condensing)
<56 dBA
230Vac single phase, 4 wires + ground / ± 15%
230Vac single phase
50Hz ± 5% (60Hz to order)
EN 50091-2 class A
230Vac single phase
Static (balanced load) ± 1%
Static (unbalanced load) ± 2%
Dynamic (step load 0-100%) ± 5%
After step load 0-100% maximum 20ms
50Hz (60Hz to order)
Line synchronised ± 1%
Free running ± 0.2%
>87-91%
3:1
Electronic short circuit
120% continuous, 150% load 10 minutes, 180% load 1 minute, 200% load for 1 second
Linear load <3%
Non-linear load 75% NP and CF 3:1) <5%
Sealed lead acid - maintenance free
26
354Vdc
260Vdc
Electronic short circuit
25°C
Weekly
Circuit breaker
TBC
TBC
  • Use basic catalogue number, e.g. HPAC8
  • Add suffix /3 for standard 3 hour duration (systems for 1 hour duration can be manufactured to order, add suffix /1)
  • Example ordering code is now HPAC8/3 (8kVA single phase static inverter system for 3 hours duration)

Specification / Technical Information

Models incorporating any of the following options are manufactured to order
  • Increased power with parallel operation
  • Increased reliability with 1+1 redundant operation
  • Additional battery modules for extension of autonomy
  • Wide Area Network management via SNMP.
  • Remote monitoring panel RM-2000
  • Modbus connection for interface with BMS Systems
  • Input / output customisation

Quick Enquiry

or call us on +44 (0) 1922 745024

0/250 Characters